Practical electrician formulas

This commonly used formulas outlined Electrotechnical theory, data, construction rules, a method of using the instrument. The reason is called electrician formulas - inspired by poetry because of the spread and easy to remember. Text in basic formulas have neat, concise, smooth, learn a rhyme of features, it would have been boring enable electrical theory and data become easy to remember.

Electrician formulas (a) easy to estimate the carrying capacity of the wire

Ten strokes five hundred on two, two hundred and fifty-three thousand five hundred forty-three sector, seven thousand and ninety-five two and a half, eight temperature of 10%, copper upgrades count.

Explanation: aluminum wire carrying capacity 10mm2 or less in terms 5A / mm; more than 100mm2 aluminum wire ampacity Press 2A / mm; an aluminum wire ampacity 25mm2 calculated as 4A / mm; an aluminum wire ampacity 35mm2 by 3A / mm is calculated; aluminum wire ampacity 70mm2,95mm2 calculated as 2.5A / mm; "upgrade copper count": for example, a copper wire ampacity calculation 120mm2 and 150mm2 can use the aluminum wire, aluminum wire carrier seeking traffic; affected by temperature and, finally, multiplied by 0.8 or 0.9 (depending on location).

Electrical formulas (II) are known transformer capacity, seeking the rated current side voltage level

Description: Suitable for any voltage level.

Formulas: capacity divided by the voltage value, the quotient by six divided by ten.

Examples: power S / 1.732 * 10KV = 1000KVA / 1.732 * 10KV = 57.736A Apparent Apparent current I =

Estimate I = 1000KVA / 10KV * 6/10 = 60A

Electrical formulas (III) are known transformer capacity, speed calculation First, the secondary protective current fuse (commonly known as a fuse) in

Formulas: high voltage distribution transformer fuse, the voltage required as compared to the capacity.

Distribution transformer low voltage fuse, capacity 5 divided by 9

Electrical formulas (IV) are known a three-phase motor capacity, rated current seek

Formulas: capacity divided by the number of volts, commercial multiplication factor 4.76.

Two hundred twenty three-phase motor is known, kW 3.5 amps.

1KW÷0.22KV*0.76≈1A

Known kV high-voltage three motors, four kilowatts one ampere.

4KW÷3KV*0.76≈1A

Note: formulas applicable to any voltage level of the three-phase rated motor current calculation. When using formulas, the unit of kW capacity, in units of kV voltage, current unit A.

Electrical formulas (e) sensing a power transformer secondary side current, load capacity request count contained in it

Known secondary pressure distribution transformer, the measured current demand kilowatts.

Four hundred volts voltage level, a safety 0.6 kilowatts.

Three thousand volts voltage level, a safety 4.5 kilowatts.

Six kV voltage level, a safety integer nine kilowatts.

Ten kV voltage level, a safety fifteen kilowatts.

Voltage level Thirty five thousand a safe fifty-five kilowatts.

Electrical formulas (VI) known small motor capacity 380V three-phase cage, seeking the minimum capacity of the power supply apparatus, a load switch, the current value of the melt protection

Direct starter motor, the capacity does not exceed ten kilowatts;

KW selected switch six times, five times with a melt kW.

KVA power supply equipment, to be three times larger number of kilowatts.

Explanation: The formulas of the motor is small 380V three phase squirrel-cage motor, motor starting current is large, typically 4-7 times the rated current. With direct starting motor load switch should not exceed the maximum capacity of 10kW, 4.5kW generally less appropriate, and open load switch (isolating switch plastic cover ceramic substrate) is generally used for small capacity and below 5.5kW motor for frequent direct starting; enclosed load switch (steel switch) generally for less frequent or less directly starting with 10kW motor. Load disconnector switch by a simple knife or melt and fuse the composition, of 6 times the rated power selection switch is appropriate; in order to avoid a large current when starting the motor, the fuse should be chosen 5 times the rated power is appropriate, i.e., rated current (a); rated current for short-circuit protection of the melt (a). Finally, select the appropriate power, the power output power not less than 3 times the rated power.

Electrical formulas (VII) sensing load current 380V single phase plate without welding transformer, its rated capacity required calculated

Formulas: three hundred eighty welder capacity, no-load current multiplied by five.

Single-phase AC welding transformer is actually a special purpose of the step-down transformer, compared with ordinary transformer, the basic working principle is substantially the same. To meet the requirements of the welding process, welding transformer working in short-circuit state, it requires a certain arc voltage during welding. When the welding current increases, the output voltage suddenly drops. The P = UI (constant power, voltage and current is inversely proportional). When the drop voltage drops to zero (i.e., the secondary-side short-circuited), the secondary side current is not caused by too large, etc., i.e., an outer welding transformer having a steep drop characteristics, the steep drop of the external characteristics of the welding transformer is generated by a reactor obtained. When the load, because no welding current through a reactor pressure drop is not generated, load voltage at this time is equal to the secondary voltage, that is the same as the general transformer load during the welding transformer load. Transformer load current is typically from about 6% to 8% of the rated current (the state load current should not exceed 10% of the rated current).

Electrical formulas (VIII) and the alternating DC current is determined

Analyzing DC electric pen, alternating bright and dark current,

Tongshen AC neon light, a neon tube DC lit end.

说明:判别交、直流电时,最好在“两电”之间作比较,这样就很明显。测交流电时氖管两端同时发亮,测直流电时氖管里只有一端极发亮。

电工口诀(九)巧用电笔进行低压核相

判断两线相同异,两手各持一支笔,

两脚与地相绝缘,两笔各触一要线,

用眼观看一支笔,不亮同相亮为异。

说明:此项测试时,切记两脚与地必须绝缘。因为我国大部分是380/220V供电,且变压器普遍采用中性点直接接地,所以做测试时,人体与大地之间一定要绝缘,避免构成回路,以免误判断;测试时,两笔亮与不亮显示一样,故只看一支则可。

电工口诀(十)巧用电笔判断直流电正负极

电笔判断正负极,观察氖管要心细,

前端明亮是负极,后端明亮为正极。

说明:氖管的前端指验电笔笔尖一端,氖管后端指手握的一端,前端明亮为负极,反之为正极。测试时要注意:电源电压为110V及以上;若人与大地绝缘,一只手摸电源任一极,另一只手持测电笔,电笔金属头触及被测电源另一极,氖管前端极发亮,所测触的电源是负极;若是氖管的后端极发亮,所测触的电源是正极,这是根据直流单向流动和电子由负极向正极流动的原理。

电工口诀(十一)巧用电笔判断直流电源有无接地,正负极接地的区别

变电所直流系数,电笔触及不发亮;

若亮靠近笔尖端,正极有接地故障;

若亮靠近手指端,接地故障在负极。

说明:发电厂和变电所的直流系数,是对地绝缘的,人站在地上,用验电笔去触及正极或负极,氖管是不应当发亮的,如果发亮,则说明直流系统有接地现象;如果发亮的部位在靠近笔尖的一端,则是正极接地;如果发亮的部位在靠近手指的一端,则是负极接地。

电工口诀(十二)巧用电笔判断380/220V三相三线制供电线路相线接地故障

星形接法三相线,电笔触及两根亮,

剩余一根亮度弱,该相导线已接地;

若是几乎不见亮,金属接地的故障。

说明:电力变压器的二次侧一般都接成Y形,在中性点不接地的三相三线制系统中,用验电笔触及三根相线时,有两根通常稍亮,而另一根上的亮度要弱一些,则表示这根亮度弱的相线有接地现象,但还不太严重;如果两根很亮,而剩余一根几乎看不见亮,则是这根相线有金属接地故障。

电工口诀(十三)----对电动机配线的口诀

口诀:2.5加三,4加四;6后加六,25 五;120导线,配百数

说明此口诀是对三相380伏电动机配线的。导线为铝芯绝缘线(或塑料线)穿管敷设。

先要了解一般电动机容量(千瓦)的排列:

0.8 1.1 1.5 2.2 3 4 5.5 7.5 1O 13 17 22 30 40 55 75 100

“2.5加三”,表示2.5平方毫米的铝芯绝缘线穿管敷设,能配“2.5加三”千瓦的电动机,即最大可配备5.5千瓦的电动机。

“4加四”,是4平方毫米的铝芯绝缘线,穿管敷设,能配“4加四”千瓦的电动机。即最大可配8千瓦(产品只有相近的7.5千瓦)的电动机。

“6后加六”是说从6平方毫米开始,及以后都能配“加大六”千瓦的电动机。即6平方毫米可配12千瓦,10平方毫米可配16千瓦,16平方毫米可配22千瓦。

“25 五”,是说从25平方毫米开始,加数由六改变为五了。即25平方毫米可配30千瓦,35平方毫米可配40千瓦,50平方毫米可配55千瓦,70平方毫米可配75千瓦。

“1 2 0导线配百数”(读“百二导线配百数”)是说电动机大到100千瓦。导线截面便不是以“加大”的关系来配电动机,而是120平方毫米的导线反而只能配100千瓦的电动机了。

电工口诀(十四)----按功率计算电流

口诀: 电力加倍,电热加半。单相千瓦,4 . 5安。单相380,电流两安半。

解释:电力专指电动机在380V三相时(功率0.8左右),电动机每千瓦的电流约为2安.即将“千瓦数加一倍”(乘2)就是电流(安)。这电流也称电动机的额定电流;电热是指用电阻加热的电阻炉等。三相380伏的电热设备,每千瓦的电流为1.5安.即将“千瓦数加一半”(乘1.5),就是电流(安);在380/220伏三相四线系统中,单相设备的两条线,一条接相线而另一条接零线的(如照明设备)为单相220伏用电设备。这种设备的功率大多为1KW,因此,口诀便直接说明“单相(每)千瓦4.5安”。计算时,只要“将千瓦数乘4.5”就是电流,安。同上面一样,它适用于所有以千瓦为单位的单相220伏用电设备,以及以千瓦为单位的电热及照明设备,而且也适用于220伏的直流;380/220伏三相四线系统中,单相设备的两条线都接到相线上,习惯上称为单相380伏用电设备(实际是接在两相线上)。这种设备当以千瓦为单位时,功率大多为1KW,口诀也直接说明“单相380,电流两安半”。它也包括以千瓦为单位的380伏单相设备。计算时只要“将千瓦乘2.5就是电流(安)。

电工口诀(十五)-----导体电阻率

导体材料电阻率,欧姆毫方每一米,

长1米,截面积1平方毫米导体的电阻值,摄氏温度为20,

铜铝铁碳依次排,从小到大不用愁。

扩大万倍来记数,铜的最小一七五,

铝的数值二八三,整整一千纯铁数,

碳的数值算最大,足足十万无零头。

电工口诀(十六)-----通电直导线和螺线管产生的磁场方向和电流方向

导体通电生磁场,右手判断其方向,

伸手握住直导线,拇指指向流方向,

四指握成一个圈,指尖指向磁方向。

通电导线螺线管,形成磁场有南北,

南极S北极N, 进行判断很简单,

右手握住螺线管,电流方向四指尖,

拇指一端即N极,你说方便不方便。

电工口诀(十七)-----阻抗、电抗、感抗、容抗的关系

电感阻流叫感抗,电容阻流叫容抗,

电感、电容相串联,感抗、容抗合电抗,

电阻、电感、电容相串联,电阻、电抗合阻抗,

三者各自为一边,依次排列勾、股、弦,

勾股定理可利用,已知两边求一边。

电工口诀(十八)-----电容串并联的有关计算

电容串联值下降,相当板距在加长,

各容倒数再求和,再求倒数总容量。

电容并联值增加,相当板面在增大,

并后容量很好求,各容数值来相加。

想起电阻串并联,电容计算正相反,

电容串联电阻并,电容并联电阻串。

说明:两个或两个以上电容器串联时,相当于绝缘距离加长,因为只有最靠两边的两块极板起作用,又因电容和距离成反比,距离增加,电容下降;两个或两个以上电容器并联时,相当于极板的面积增大了,又因电容和面积成正比,面积增加,电容增大。

电工口诀(十九)-----感性负载电路中电流和电压的相位关系

电源一通电压时,电流一时难通达,

切断电源电压断,电流一时难切断,

上述比喻较通俗,电压在前流在后,

两者相差电角度,最大数值九十度。

电工口诀(二十)-----三相电源中线电流、相电流和线电压、相电压的定义

口诀:三相电压分相、线,火零为相,火火线,

三相电流分相、线,绕组为相,火线线。

对于三相电源,输出电压和电流都有相和线之分,分别叫“相电压”,“线电压”,“相电流”,“线电流”。相电压是指火线和零线之间的电压,火线与火线之间的电压叫线电压;相电流是指流过每一相绕组的电流,线电流是流过每一条火线的电流。

电工口诀(二十一)三相平衡负载两种接法中的线电压和相电压,线电流和相电流的关系

电压加在三相端,相压线压咋判断?

负载电压为相压,两电源端压为线。

角接相压等线压,星接相差根号三。

电压加在三相端,相流线流咋判断?

负载电流为相流,电源线内流为线。

星接线流等相流,角接相差根号三。

解释:当我们画出简单的示意图,就不难看出角接实际上就是两个电阻并联(把两个电阻串联看成为一个总电阻),根据并联电路的特点,相电压等于线电压;当接法为星接时,就可以看成是两个电阻串联(把其中两个并联电阻看成一个总电阻),线电流等于相电流。只要记住线大于相,因为相电流、相电压均为负载的电流与电压,线电流、线电压为电源两侧的电流与电压。

电工口诀(二十二)-----已知变压器容量,求其电压等级侧额定电流

常用电压用系数,容乘系数得电流,

额定电压四百伏,系数一点四四五,

额定电压六千伏,系数零点零九六,

额定电压一万伏,系数刚好点零六。

注解:可直接用变压器容量乘以对应的系数,即可得出对应电压等级侧的额定电流。

电工口诀(二十三)-----根据变压器额定容量和额定电压选配一、二次熔断器的熔体电流值

配变两侧熔体流,根据容量简单求,

容量单位千伏安,电压单位用千伏。

高压容量除电压,低压乘以一点八,

得出电流单位安,再靠等级减或加。

举例:三相电力变压器额定容量为315KVA,高压端的额定电压为6KV,低压端的额定电压为400V;

高压侧熔体的额定电流为(315÷6)A=52.5A;低压侧熔体的额定电流为(315×1.8)A=567A

注:选择熔断器的规格,应根据计算值与熔体电流规的差值来决定。

电工口诀(二十四)-----根据变压器额定电流选配一、二次熔断器的熔体电流值

配变两侧熔体流,额定电流数倍求,

高压一侧值较大,不同容量不同数。

容量一百及以下,二至三倍额流数,

一百以上要减少,倍数二至一点五,

高压最小有规定,不能小于三安流,

低压不分容量值,一律等于额定值。

电工口诀(二十五)-----配电变压器的安装要求

距地最少两米五,落地安装设围障,

障高最少一米八,离开配变点八强,

若是经济能允许,采用箱式更妥当,

除非临时有用途,不宜露天地上放,

室内安装要通风,周围通道要适当。

电工口诀(二十六)-----对配电变压器供电电压质量的规定

供电电压有保障,设备运行才正常

高低偏差有规定,电压高低不一样,

线间电压正负七,负十正七压为相,

如果要求较特殊,供需双方来商量。

注解:我国低压供电系统中,线电压为380V,允许偏差±7﹪,即353.4~406.6V;相电压为220V,允许偏差-10﹪~+7﹪,即198~235.4V。

电工口诀(二十七)-----变压器的绝缘绕组检测

变配运行保安全,测量绝缘查隐患。

测量使用兆欧表,根据电压把表选。

超过三五两千五,十千以下用一千。

仪表E端应接地,污染严重加G端。

未测绕组和元件,可靠接地保安全。

手摇转速一百二,测后放电再拆线。

注解:对于35KV及以上的变压器应使用2500V的兆欧表;10KV及以下的变压器应使用1000V的兆欧表,L端接变压器的绕组,E端接地。

电工口诀(二十八)-----两台变压器的并列运行

并列两台变压器,四个条件要备齐;

接线组别要相同,要有相同变压比;

阻抗电压要一致,相互连接同相序;

容量相差不宜多,最好不超三比一。

电工口诀(二十九)-----配电变压器熔丝熔断的原因

高压熔丝若熔断,六个原因来判断。

熔丝规格选的小;质劣受损难承担;

高压引线有短路;内部绝缘被击穿;

雷电冲击遭破坏;套管破裂或击穿。

低压熔丝若熔断,五个原因来判断。

熔丝规格选的小;质劣受损难承担;

负荷过大时间长;绕组绝缘被击穿;

输电线路出故障,对地短路或相间。

电工口诀(三十)-----交流电焊机空载耗损的估算值

三百八十电焊机,空损瓦数可估计。

若知容量伏安数,除以五十就可以。

容量单位千伏安,改乘二十来计算。

若知空载安培数,扩大百倍及可以。

Guess you like